Thông tin sản phẩm

MZSR-600PVI/PVY

 

MZSR-600PVI  

IEC Class II compliant

Surge Protective Device (SPD) for a power supply circuit (up to DC 600V) which is used for Solar Power System.

PVI type for a circuit with earthing, PVY type for a circuit with no earthing.

 
Connection example
   
With earthing:MZSR-600PVI No earthing:MZSR-600PVY
MZSR-600PVI_e2.jpg MZSR-600PVY
 
 

MZSR-600PVI

 

MZSR-600PVI_s2.jpg

zoom

 

IEC Class II compliant
RoHS compliant

[Dimension] W36*D99*H81

 

Maximum discharge current : 40kA(8/20μs)

Built-in DC fuse with deterioration display

PVI type for DC circuits with earthing

Plug-in type for easy replacement

Deterioration display with warning output terminal

DIN rail mountable (35mm)

 
Main performance characteristics
 
Item Performance
Applicable lines   DC 600V
with earthing
Maximum continuous operating voltage Ucpv *   DC 720V
Maximum discharge current Imax 8/20μs 40kA
Nominal discharge current In 8/20μs 20kA
Voltage protection level Up Based on IEC Less than 3,000V
Voltage protection level Up (5kA) Based on IEC Less than 2,500V
*It can't be used if open voltage is over Ucpv.
 
 

MZSR-600PVY

 

MZSR-600PVY

zoom

 

IEC Class II compliant
RoHS compliant

[Dimension] W54*D99*H81

 

Maximum discharge current : 40kA(8/20μs)

Built-in DC fuse with deterioration display

PVY type for DC circuits with no earthing

Plug-in type for easy replacement

Deterioration display with warning output terminal

DIN rail mountable (35mm)

 
Main performance characteristics
 
Item Performance
Applicable lines   DC 600V
with no earthing
Maximum continuous operating voltage Ucpv *   DC 720V
Maximum discharge current Imax 8/20μs 40kA
Nominal discharge current In 8/20μs 20kA
Voltage protection level Up Based on IEC Less than 3,000V
Voltage protection level Up (5kA) Based on IEC Less than 2,500V
*It can't be used if open voltage is over Ucpv.