Thông tin sản phẩm

Loại CX-E-ECS

 

CX-E-ECS type

Zoom

 

Category C2, Category D1 compliant
(CX-H-ECS-2 is Category C2 compliant only)

SPD for co-axial connectors with BNC type connectors for the protection of co-axial cable connected monitor cameras, etc., from lightning surge and other kinds of irregular voltage.
·Guarantees high frequency bandwidth protection up to 30MHz, and achieves a high level of protection performance.
·DIN rail (35mm) mountable configuration

RoHS compliant

[Dimensions] W95×D38×H40

 
 
Main performance characteristics
 
Item Conditions Performance characteristics
CX-E-ECS CX-H-ECS-1
Connectors BNCtype
Frequency bandwidth DC to 30MHz
Impedance 50Ω/75Ω
Insertion loss DC to 30MHz 1.0dB or less
Maximum continuous operating voltage  Uc Between core conductor and external conductor DC58V or less
Rated current 1A
Breakdown voltage 1mA
(Between core conductor and external conductor)
75V or less
100V/s peak hold
(Between conductors and earths)
260V or less
Voltage protection level Up 1.2/50μs10kV 250V or less
(Between core conductor and external conductor)
500V or less
(Between conductors and earths)
Impulse durability CategoryC2 8/20μs 10kA
CategoryD1 10/350μs 5kA
Insulation resistance DC100V
(Between core conductor and external conductor)
100MΩ or more
DC58V
(Between conductors and earths)
58MΩ or more
AC durability 50Hz 0.5A 1sec. 5 times
DC resistance 1A
(Between core conductor line and equipment)
1Ω±20%
Overload failure mode Mode 2
 
Item Conditions Performance characteristics
CX-H-ECS-2
Connectors BNCtype
Frequency bandwidth DC to 30MHz
Impedance 50Ω/75Ω
Insertion loss DC to 30MHz 1.0dB or less
Maximum continuous operating voltage Uc Between core conductor and external conductor DC58V or less
Rated current 1A
Breakdown voltage 1mA
(Between core conductor and external conductor)
75V or less
100V/s peak hold
(Between conductors and earths)
Voltage protection level Up 1.2/50μs10kV 250V or less
(Between core conductor and external conductor)
Impulse durability CategoryC2 8/20μs 10kA
CategoryD1 10/350μs
Insulation resistance DC58V
(Between core conductor and external conductor)
58MΩ or more
AC durability 50Hz 0.5A 1sec. 5times
DC resistance 1A
(Between core conductor line and equipment)
1Ω±20%
Overload failure mode Mode2