Bộ biến áp cách ly

 

Insulation transformer unit UT type

拡大

 

UT10P66 type
This device is installed on the service wires of carrier transmission system substation remote monitoring equipment and communication breakers, etc., to protect people and equipment from ground potential rise that may occur in the event of a substation accident, etc., or irregular voltage such as lightning surges, that may have been induced along link lines, as well as to prevent damage to line insulation.

UT10S11 type
This device is used to protect people and equipment from irregular voltage caused, for example, by potential rise in the event of a feed circuit earth fault, or by lightning surges induced into the transmission circuits between ATS-P device code processing equipment, or other signal transmission circuits.

 

【Dimensions】 W166×D116×H110

 
Main performance characteristics
 
Item Performance characteristics
UT10P66 UT10S11
Capacity 0.3 to 3.4kHz 3 to 9kHz
Signal level 10dBm
Impedance ratio
Equipment side:track side
600Ω:600Ω 150Ω:150Ω
Impedance deviation ±10% ±10%
Operating attentuation 0.5dB or less 0.7dB or less
Withstand voltage Between L1, L2 and T1, T2 AC10kV 1 min.
impulse 1.2/50μs 25kV 3 times
Between L1, L2 and Es
Between T1, T2 and Es AC3kV 1 min.
Impulse protection level Between earths, between lines 10/200μs
3kV applied at 50V or less
AC protection level 50V or less applied at AC500
Impulse life 10/200μs, 400A, 100 times 10/200μs, 200A, 100 times
AC life Applied at AC (50/60Hz)
20A, 0.1s, 10 times
Applied at AC (50/60Hz)
10A, 0.1s, 10 times
Impulse discharge current withstand capacity 10/200μs, 5,000A 10/200μs, 2,500A
AC withstand capacity 20A, 1s applied at AC (50/60Hz) 10A, 1s applied at AC (50/60Hz)
Insulation resistance Between L1, L2 and T1, T2 100MΩ or more at DC250V 100MΩ or more at DC250V
Between L1, L2 and E -
Between L1, L2 and Es 100MΩ or more at DC250V
Between T1, T2 and Es